Maintenance Of Wind Direction Sensor; Specifications - Priva Compass Installation Manual

Table of Contents

Advertisement

Priva

Maintenance of wind direction sensor

Check the wind direction sensor regularly for pollution and clean it if necessary. Pollution may cause
the wind vane to be obstructed. Clean the unit with a damp cloth and a little mild detergent if required.
Do not use aggressive cleaning agents or abrasives.
Make sure that no moisture, dirt or dust enters the housing when opening the Wind direction
sensor. This can negatively impact the measurement.

Specifications

Article description
Article number
Measurement principle
Wind direction
Resolution
Measuring error
Measurements/sec
Output signal
Output range
Supply voltage
Power consumption
Protection
Ambient temperature
The output signal is divided across seven measurement zones, including two defect zones. See the
table below.
Output voltage (mV)
0 – 200
200 – 920
920 – 1640
1640 – 2360
2360 – 3080
3080 – 3440
3440 – 4096
74
Wind direction
Defect
North – East
East – South
South – West
West – North
North – North-east
Defect
Wind direction sensor
3779215
optical or magnetic
0 – 359°
20
Single ended
200 - 3440 mV
18 – 40 VDC
15 mA (max)
Continuous 24 VAC
Discharges 900 V/100 nF
Short circuit-proof output
-40 – +80 °C
Installing Priva Compass - 00.014