Priva Compass Installation Manual page 28

Table of Contents

Advertisement

Priva
Tab: I/O connection
The software has been distributed across the zones and equipment must be connected to the
controller on the I/O connection tab.
Before we can allocate the inputs and outputs, check whether Compass setup is detecting the correct
hardware. On the left-hand side, you will see the hardware modules that are detected. If these match
the modules that are present, confirm them with Confirm.
If the modules displayed do not match what has been installed, check the cabling between the
modules and whether the controller (CMX34) and the extension module (MX34) are switched on.
After confirming the hardware module layout, you will also see a blue LED illuminate on each module.
You can now allocate sensors/actuators to the inputs and outputs for each zone. The list box for the
sensors/actuators depends on the licence and the assignment of the software modules to the zones.
Next, select the hardware module and the input or output for this sensor/actuator to which you
wish to connect the sensor/actuator. The software will display a suggestion. Select Assign to save the
assignment.
After allocating the inputs and outputs, save the list of I/O connections as an Excel file, as a
PDF file or as a file that can be imported on the same or a different controller (select Export).
Other controller settings
In the top right-hand corner of Compass setup you will see the
mains power supply (50 or 60 Hz), the buzzer volume and the option for updating the controller
software (Upload platform image).
At the top right of Compass setup there is also the
to Gateway setup. Select this once Compass setup has been completed.
You will return to the Settings tab of Gateway setup.
To include the configured controller in the operating software, the final step is to connect this
controller to the Gateway by selecting Connect on the controller.
Repeat this procedure within Compass setup for each controller in the Compass system.
Once all the controllers have been commissioned, disconnect your laptop if you are connected to
the Gateway with an Ethernet cable. If the Compass is being operated via the office network or with
a Wi-Fi router for direct wireless operation, connect the Gateway's Ethernet port 1 to your office
network.
Starting operation
To start the operating software, select the Gateway's IP address in the address bar of a browser.
Go to Settings to set the latitude and longitude of the location in which the Compass has been installed.
This is important in order to synchronise the set times with the sunrise and sunset times.
26
button for the frequency of the
button for exiting Compass setup and returning
Installing Priva Compass - 00.014