Cross-section of Rain sensor
1. Contact surface + heating
2. Printed circuit board (9583)
The Rain sensor is supplied with a 10-metre shielded cable. It is recommended that you do
not shorten this cable when mounting the unit. Coil the remaining length of cable or leave
a loop; This ensures that the cable will not be too short in the event of eventual extensions
with supports and mast components.

Connecting

See
Connecting sensors to the Weather interface WI2 (page 58)

Speeding up the initial rain detection

After the connection and commissioning of the Rain sensor, the electronic systems require some
time before the rain detection functions properly. This time can be as long as 60 minutes when the
grid is dry. You can reduce this time to 1 minute as follows:
1.
Place a clean wet sponge with tap water on the cartridge. Do not use demineralised water,
because it is not conductive.
The Rain sensor should detect rain after 1 minute.
2.
Remove the sponge.
A short time after this, the Rain sensor should no longer detect rain.

Rain sensor maintenance

Clean the rain sensor at least once a year, or earlier if the Rain sensor develops measurement
deviations (for instance, due to leaves or bird droppings). Clean the unit with a damp cloth and a
little mild detergent if required. Also check for corrosion or any other damage to the surface of the
sensor. Replace the sensor if the surface has been damaged.
Do not use aggressive cleaning and/or abrasives. This damages the gilded contact surface
of the Rain sensor.
Make sure that no moisture, dirt or dust enters the housing when opening the Rain sensor.
This can negatively impact the measurement.