Please note that the office network may not automatically issue an IP address. In that case, use an
IP address for Ethernet 1 in the same range as the office network.
Ethernet 2 is the Priva industrial network for the controller(s). Use a different IP range for this network
than that of your office network, e.g. 172.17.16.80.
It is possible that Ethernet 3 is now being used for the Wi-Fi network with the dongle. Apart from
that, it is not used.
Tab: preferences
Set your preferences here for the language of the local Operator and the units used.
Compass setup
Update device
On the Settings tab of Gateway setup you can see the controllers that the Gateway has detected in
the Priva network.
Select Update device. You will now be taken to Compass setup.
The controller's IP address must be in the same range as Ethernet port 2 of the Gateway to which
the controller is connected, e.g. 172.17.16.85. Change the controller's IP address by clicking on
next to the IP address. You can change the IP settings by typing them yourself or by selecting Auto
assign. Once the changed settings have been saved, the controller needs some time to implement
the changes.
Click on the
Select Upload platform image to update the software with the Controller Setup file from the preparation
stage. The file will then be uploaded to the controller, which verifies the file. You will then be prompted
to confirm the update. The controller update process takes approximately 5 minutes.
Tab: network
After updating the controller software, you will see the Network tab of Compass setup where you can
adjust the network settings. This has already been done and you can proceed to the next step.
Tab: zones
On the Zones tab you can add the zones. A zone can be used as a zone for the climate area and at
the same time as an area for a water system, for instance.
Each controller can contain a maximum of 4 zones. When adding a zone, select the zone number
that you wish to use. These numbers do not have to be consecutive, but must always be unique
within the Compass system, including in the event that there are several controllers.
Select Save to save the zone configuration.
Tab: software
Once the zones have been added, enter the licence code on the Software tab and confirm it with
Submit.
On the left-hand side of the browser page, you will then see the software options that have been
enabled by the licence code. On the right-hand side, you will see the zones that have been added
and the available software modules. You can distribute the software modules across the zones and
then click on Save.
Installing Priva Compass - 00.014
button in the top right-hand corner of Compass setup.
Compass system installation steps
25