Preconditions For Installation And Use - Priva Compass Installation Manual

Table of Contents

Advertisement

Priva

Preconditions for installation and use

IP code (NEN-EN-IEC 60529)
Permitted ambient temperature during
normal operation
Permitted ambient relative humidity
during normal operation
Pollution factor (NEN-EN-IEC 61010-1)
Permitted temperature for transport
and storage
Permitted ambient relative humidity
for transport and storage
Maximum temperature inside cabinet
during normal operation
Maximum heat generated in cabinet
Installation
Other installation and environmental
requirements
Maximum installation height
Installation category
122
Compass 2S
IP 66
0 ... 35 °C
10 ... 95 % (non-condensing)
2 (normal, non-conducting pollution)
-25 ... 70 °C
0 ... 95 % (non-condensing)
50 °C
57 W at maximum permitted ambient
temperature (active cooling is required
if more heat is generated)
on the wall using four mounting holes
using 4 M8 bolts (minimum length 5 cm) (not included)
do not expose to direct sunlight
do not install close to a heat source or outdoors
2000 meters above sea level
II
Compass 4S
75 W at maximum permitted ambient
temperature (active cooling is required
if more heat is generated)
Installing Priva Compass - 00.014

Advertisement

Table of Contents
loading

Table of Contents