Priva Compass Installation Manual page 135

Table of Contents

Advertisement

Universal input - Other
Functional isolation of inputs in relation to system
neutral
Maximum current of FG connections
Indication (for modules with manual override or
indication only)
Analogue outputs
Output voltage control range
Maximum load current supplied per output
(source)
Maximum current load drawn per output (sink)
Load resistance
Resolution
Accuracy
Accuracy of feedback
Adjustment time
Input leakage current with high impedance
output¹
Protection
Number of switch-on attempts in the event of
short circuit or overload²
Functional isolation of outputs in relation to
system neutral
Maximum current of FG connections
Indication (for modules with manual override only) •
Controls (for modules with manual override only)
¹ The output is high impedance ex-factory; the module has not yet been configured then. In addition, unused
outputs and the outputs where the overload protection has been activated are high impedance.
² After a short-circuit or overload the output is switched back on after 0.5 s. The output switches back off
immediately if the overload is still present. The output performs a maximum of 5 switch-on attempts with a time
interval of 0.5 seconds. After 5 attempts, the output is switched off and manual intervention is required.
Installing Priva Compass - 00.014
General specifications of Priva Blue ID C-Line controllers and modules
250 V
10 A
green/red LEDs for status of inputs for digital use (colour is
adjustable)
0 ... 10 V
5 mA
> 2 kΩ
600 µV (> 13 bits over 10 V)
± (10 mV + 0.5% of the control signal)
± 150 mV
200 ms (to 70% of the set value)
maximum 5 µA
output is short-circuit proof (self-restoring after a brief short
circuit/overload)
output is protected against ± 30 VDC and 30 VAC
5
250 V
10 A
orange LEDs for indication of output voltage
orange LED for status of control (automatic or manual)
buttons to set the voltage level of the output manually:
+: manually increase output voltage
A: automatic control of output voltage
-: manually decrease output voltage
133