Rexroth IndraDrive CsDrive Systems with HCS01
Equipment grounding conductor
DC bus
Arrangement

Operation

Mains Choke
DC bus coupling
Connect the equipment grounding conductor via thread M5 to the housing of
the device (identification mark
screw required for this purpose is part of the supplied accessories HAS09.
Connect HLC01 to HCS01 with twisted lines: L+ to L+; L- to L-
Technical data of the connection point: See description of
X77.
Place the HLC next to the most powerful drive controller of a drive system.
Always operate the DC bus capacitor units together with the mains choke as‐
signed to the drive controller (see
233).
Special case "HCS01.1E-W0018-_-03" (in the technical data, no mains choke
has been assigned to this drive controller):
Use the mains choke "HNL01.1E-1000-N0012-A-500-NNNN".
Information on DC bus coupling: See
page 111
Bosch Rexroth AG
Cables, accessories, additional components
; tightening torque: 5 Nm). The M5×12
chapter 7.3.2 "Mains voltage" on page
chapter "DC Bus Capacitor Unit" on
311/341
connection point