Tions - Bosch Rexroth IndraDrive CsDrive System with HCS01 Project Planning Manual

Hide thumbs Also See for Rexroth IndraDrive CsDrive System with HCS01:
Table of Contents

Advertisement

150/341
Bosch Rexroth AG
Mounting and installation
HCS01.1E-xxxxx-x-03
View
Spring terminal (connector)
Connection cable
Stranded wire
Stripped length
Contact rating
Module bus connections
Technical data
Connec‐
tion
1
2
3
4
5
6
Unit
mm
2
AWG
mm
V
A
1)
Wire the Bb relay contact in the control circuit for mains con‐
nection (see
on page
104). When the contact opens, the mains contactor
must interrupt the power supply. If multiple devices supply the
DC bus (group supply), connect the Bb relay contacts (X47) of
all supplying devices in series.
2)
The pins 3, 4 and 5, 6 are jumpered. This allows the module
bus to be looped through from one device to the next.
Tab. 6-18:
Function, pin assignment, properties
Maximum allowed length of an individual module bus connection: 10 m
In the following cases, use shielded cables for the module bus connection:
The length of an individual module bus connection is > 0.5 m.
The total length of all module bus connections of the drive system is
> 3 m.
Use shielded cables with a conductor gauge ≥ 2 × 0.5 mm
Accessory for shield connection: HAS09.1-001-NNN-NN (see
ule bus cable shield connection" on page
chapter "Relay Contact Type 2" on page 229
DOK-INDRV*-HCS01******-PR05-EN-P
Rexroth IndraDrive CsDrive Systems with HCS01
Signal name
Rel1
Rel2
Mod1
Mod2
0V_Mod
0V_Mod
min.
0.2
24
10
0.01
chapter "Control Circuit for the Mains Connection"
256).
Function
Bb relay contact
1)
Bb relay contact
1)
Module bus
2)
Module bus
2)
Module bus GND
2)
Module bus GND
2)
max.
1.5
16
30
1
2
.
chapter " Mod‐

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents