Rexroth IndraDrive CsDrive Systems with HCS01
Closed control cabinet with
air circulation
P
~ 400 W
Q
Requirements for control cabinets
with fan
Possibilities of heat dissipation
Closed control cabinet with
heat exchanger
P
~ 1700 W
Q
P
Dissipated heat output
Q
Tab. 4-14:
Possibilities of heat dissipation
The section below describes the "control cabinet with fan".
NOTICE
Operating a control cabinet with a fan, but without the corresponding filters,
can damage the devices or cause malfunction.
Install filters at the air intake opening of the control cabinet so that un‐
clean air cannot get into the control cabinet.
Service the filters at regular intervals according to the dust loading in the
environment.
Only replace the filters when the fan has been switched off, because
otherwise the fan sucks in the dirt coming off the filter and the dirt gets
into the control cabinet.
Bosch Rexroth AG
Combining the individual components
Control cabinet with fan
P
~ 2700 W
Q
Risk of damage by unclean air in the control
cabinet!
57/341
Closed control cabinet with
air conditioning unit
P
~ 4000 W