Channel-Specific Module Parameters - Monitoring Wire Break - Festo CPX Series Manual

Terminal, analogue i/o modules, sub-bases
Hide thumbs Also See for CPX Series:
Table of Contents

Advertisement

8. Analogue output module CPX-2AA-U-I
1
End value of the
data range
2
Lower limit
3
Upper limit
4
Less than or
exceeding the limits
Fig. 8/7: Monitoring of limits with the "Fixed value" data formats
8.4.6 Channel-specific module parameters – Monitoring wire break
Festo P.BE-CPX-AX-EN en 1107f
Limits with the "Fixed value" data formats
The following diagram shows an example of the data format
"VZ + 12 bits right-justified" with the scaling end values:
Lower limit = 500
Upper limit = 3500
The principle of the limits also applies to the data formats
"VZ + 15 bits left-justified" and "VZ + 12 bits left-justified".
1
2
0
500
Wire break/open loop monitoring can be activated by means
of appropriate parameterisation for the signal range
0/ 4 ... 20 mA. The messages are made available as diagnos-
tic information (see section 8.5.1).
3
1
3500
4095
4
8-31