Error Messages Of The Analogue Input Modules - Festo CPX Series Manual

Terminal, analogue i/o modules, sub-bases
Hide thumbs Also See for CPX Series:
Table of Contents

Advertisement

3. Analogue input module CPX-4AE-U-I

3.5.1 Error messages of the analogue input modules

Error no.
Description
2
Error short circuit/overload
Short circuit/overload in sensor supply
(V
EL/SEN
(see parameter "Monitoring the CPX
module – monitoring SCS" in Tab. 3/7)
Wire break at current input
3
Only for voltage inputs with signal
range 4 ... 20 mA: The input current I
is less than 1.2 mA.
(see parameter "Monitoring channel x
– monitoring wire break")
9
Value below nominal range
Lower limit exceeded.
(see parameter "Lower limit channel x
– low byte/high byte" or "Monitoring
channel x – monitoring value below
nominal range")
1)
The module will report the appropriate error depending on the parameterisation. The analogue
input signals will, however, be processed further.
Tab. 3/22: Error messages of the CPX-4AE-U-I module - part 1
3-32
The CPX-4AE-U-I module can register the following errors:
1)
).
1)
1)
Error handling
1. Eliminate short circuit/overload or check
connected sensors
2. Depending on parameterisation (para-
meter "Behaviour after short circuit"):
Setting "Switch voltage on again":
Power supply for sensors will be
switched on again automatically when
the short circuit is eliminated.
Setting "Leave voltage switched off":
– Power Off/On necessary
or
– Modify parameter "Behaviour after
short circuit" to "Switch voltage on
again".
Check and, if necessary, replace the cable
and connected sensors.
IN
Check signal range of input.
Check input signal present.
Check parameterised limit value.
If necessary, deactivate monitoring.
Festo P.BE-CPX-AX-EN en 1107f