Festo CPX Series Manual page 218

Terminal, analogue i/o modules, sub-bases
Hide thumbs Also See for CPX Series:
Table of Contents

Advertisement

6. Analogue input module CPX-4AE-TC
Module parameter: Monitoring open load/short circuit
Function no.
4828 + m * 64 + 7 (channel 0 ... 3);
Description
Defines whether or not a diagnostic message is to be displayed after wire open
load or short circuit. The parameter can be set for the individual channels
independently of each other.
Bit
Diagnosis of open load/short circuit sensor
Bits 0/1: channel 0
Bits 2/3: channel 1
Bits 4/5: channel 2
Bits 6/7: channel 3
Values
Channel 3
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
0
00 = disabled (presetting)
01 = enabled
Tab. 6/13: Monitoring open load/short circuit (channel-specific)
6-24
Channel 2
Channel 1
0
0
0
0
1
0
1
0
Handheld display
m = module number (0 ... 47)
[Monitoring OL/SC Sensor]
Channel 0
0
0
0
No diagnostic message
(presetting)
1
0
1
Diagnostic message in the
event of open load or
short circuit
[Disabled]
[Enabled]
Festo P.BE-CPX-AX-EN en 1107f

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents