Parameterisation
3.3.3
Wire Break Diagnostics
The parameter "Wire break diagnostics" defines whether the diagnostics for the input signals must be
activated or deactivated with regard to a shortfall of the input current.
When the diagnostics are activated, the error at an input current of <1.2 mA will be sent to the bus
module and displayed with the error LED on the module.
The parameter is only effective with a defined signal range of 4 ... 20 mA è Tab. 30 .
Channel parameter – Wire break diagnostics
Setting
Channel 0
Deactivate diagnostics