7. Pressure sensor module CPX-4AE-P
7.5.1 Error messages of the pressure sensor module CPX-4AE-P
Error
Description
number
9
Limit value underrun
10
Limit value overrun
27
Incorrect device type fitted
29
Parameterisation error
An error has occurred in the setting of a
parameter (monitored parameters:
see Tab. 7/3).
51
Sensor limit diagnostics
Physical limit value of a sensor has been
exceeded
– Process value invalid (see error
number 55) The output measured value
no longer corresponds to the physical
pressure present
– Hardware damage is possible
55
Invalid process value
Creation of the process value is not valid:
e.g. during the differential pressure
calculation (see Tab. 7/5), if the sensor
limit diagnostics are signaled for one of
the pressure sensors.
1)
The module will register the appropriate error depending on the parameterisation.
However, the input signals will be processed further.
2)
The (faulty) parameters entered will be ignored; the module operates with the last valid
parameters.
Tab. 7/13: Error messages of the pressure sensor module CPX-4AE-P
7-24
The pressure sensor module CPX-4AE-P can notify the
following errors:
1)
2)
Error handling
Check compressed air supply
Check the parameterisation
(see Tab. 7/9 and Tab. 7/10)
Undertake planned remedy
Servicing required
Check the parameterisation made and if
necessary make the parameterisation
again with the correct parameters
(valid parameters see Tab. 7/2)
Ensure that the maximum permitted
pressure is not exceeded
Check module for damage; replace if
necessary
See error number 51
Festo P.BE-CPX-AX-EN en 1107f