Festo CPX Series Manual page 65

Terminal, analogue i/o modules, sub-bases
Hide thumbs Also See for CPX Series:
Table of Contents

Advertisement

2. Analogue input module CPX-2AE-U-I
Channel parameters: Signal range channel x
Function no.
4828 + m * 64 + 8
Description
For the individual channels of the analogue input modules, the signal ranges of
the analogue inputs can be set independently of each other.
Bit
Bit 0/1:
Bit 2/3:
Bit 4/5:
Bit 6/7:
Values
Channel 0
Bit 3 Bit 2 Bit 7 Bit 6
0
0
1
1
Comment
Bits 0/1 as well as 4/5 represent the status of the DIL switches for setting the
signal range.
With bits 2/3 and 6/7 other signal ranges can be parameterized irrespective of
the DIL switch setting.
Modified parameter settings have precedence over the DIL switch settings.
The setting of the DIL switches is carried out with the presetting (bit 2/3 = 0;
bit 6/7 = 0).
Tab. 2/14: Signal range channel x
Festo P.BE-CPX-AX-EN en 1107f
setting of DIL switch 0 for channel 0 (read only)
switch 0.1 = bit 0
switch 0.2 = bit 1
signal range channel 0 (AI0)
setting of DIL switch 1 for channel 1 (read only)
switch 1.1 = bit 4
switch 1.2 = bit 5
signal range channel 1 (AI1)
Channel 1
0
0
0
Using the setting of the DIL switches (presetting)
1
0
1
0 ... 10 V
0
1
0
0 ... 20 mA
1
1
1
4 ... 20 mA
m = module number (0 ... 47)
2-21

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents