Advertisement

5. Analogue input module CPX-4AE-T
5.4.4 Monitoring wire break/short circuit
5.4.5 Limit value monitoring by means of parameterisation
Parameterisation
of the limit value
1)
monitoring
"No diagnosis"
"Message if limit value is
not reached"
"Message if limit value is
exceeded"
1)
See Tab. 5/11
2)
See Tab. 5/15
Tab. 5/17: Effect of limit value monitoring on the diagnostic messages
Festo P.BE-CPX-AX-EN en 1107f
Wire break (Open Loop) and short-circuit monitoring can be
activated by means of appropriate parameterisation
(see Tab. 5/10).
With the channel-specific parameters "Definition limit value"
(parameters 15 ... 22) you can define a limit value for each
channel. With the parameter "Limit value monitoring" (para-
meter 8) you can define whether a diagnostic message is to
be displayed when the limit value is exceeded or not reached.
Note
If you are using a different temperature sensor from the
Pt 100: Set the sensor used with the parameterisation.
Monitoring of the sensor temperature range functions
correctly as follows:
2)
Set limit value
is not reached
No message
Diagnostic message
error no. 9
No message
2)
Set limit value
is exceeded
No message
No message
Diagnostic message
error no. 10
Sensor
temperature range
No message
Diagnostic message
If limit value is not
reached 9
If limit value is
exceeded 10
5-25