8. Analogue output module CPX-2AA-U-I
Module parameters: Idle mode channel x
Function no.
Access to these module parameters is made via protocol-specific functions
(see the manual for the field bus node).
Description
The Idle mode parameterisation is only relevant with certain field bus protocols.
With the aid of the so-called Idle mode, you can determine the signal status
which the outputs are to assume when the Idle function is accessed (see also
CPX system manual). This can be accomplished with the following parameters:
– Idle mode channel x
– Idle state channel x
Values
– Idle mode channel x:
– Idle state channel x:
Comment
The parameterisation of the Idle mode for an analogue output channel is accom-
plished in the case of the field bus node CPX-FB11 by means of an individual
parameter setting or bit.
For parameterisation of the Idle state, the desired output word must be
correspondingly mapped in the parameter bits "Idle state channel x".
The Idle mode reaction is determined for the complete CPX terminal by means of
the system parameter "System Idle mode" (see CPX system manual).
Tab. 8/17: Idle mode channel x (channel specific)
8-24
0 = Hold last state
1 = Idle state (presetting)
0 = Reset value (presetting)
1 = Set value