Parameter Descriptions
Point B: After some time the cut-out level may be reached
and the compressor must be shut off.
Point C: Cut-in is reached and the compressor is restarted.
NOTE
When using the TPF together with the Cascade Controller
further consideration must be taken. The Cut-Out value
should be below the Override Bandwidth setting (see
25-21 Override Bandwidth). Cut-In should be set above the
set-point and below the value for Staging Bandwidth (see
25-20 Staging Bandwidth).
7-80 Thermostat/Pressostat Function
Option:
Function:
[0]
Off
Function is inactive
*
[1]
On
Function is active
7-81 Cut-out Value
Range:
Function:
1 bar
[-3000 - par.7-82] Select the Cut-out Level where the
*
stop signal is activated and the
compressor stops.
7-82 Cut-in Value
Range:
Function:
3 bar
[Par.7-81 –
Select the Cut-in Level where the stop
*
3000]
signal is de-activated and the
compressor starts.