General Specifications
The RS-485 serial communication circuit is functionally separated from other central circuits and galvanically isolated from
the supplier voltage (PELV).
Control Card, USB Serial Communication
USB standard
USB plug
Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. The USB
ground connection is not galvanically isolated from protection earth. Use only isolated laptop as PC connection to the USB
connector on the frequency converter drive
Relay Outputs
Programmable relay outputs
Relay 01 Terminal number
Max. terminal load (AC-1)1) on 1-3 (NC), 1-2 (NO) (Resistive load)
Max. terminal load (AC-15)1) (Inductive load @ cosφ 0.4)
Max. terminal load (DC-1)1) on 1-2 (NO), 1-3 (NC) (Resistive load)
Max. terminal load (DC-13)1) (Inductive load)
Relay 02 (CDS302 only) Terminal number
Max. terminal load (AC-1)1) on 4-5 (NO) (Resistive load)
Max. terminal load (AC-15)1) on 4-5 (NO) (Inductive load @ cosφ 0.4)
Max. terminal load (DC-1)1) on 4-5 (NO) (Resistive load)
Surroundings
Enclosure ≤ enclosure type A
Enclosure ≥ enclosure type A, B
Enclosure kit available ≤ enclosure type A
Vibration test
Max. relative humidity
Aggressive environment (IEC 721-3-3), uncoated
Aggressive environment (IEC 721-3-3), coated
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature
Derating for high ambient temperature, see section on special conditions
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance
Temperature during storage/transport
Maximum altitude above sea level without derating
Maximum altitude above sea level with derating
Derating for high altitude, see section on special conditions
EMC standards, Emission
EMC standards, Immunity
MG34M302 - VLT
®
Operating Instructions VLT
5% - 95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
®
is a registered Danfoss trademark/Commercial Compressor
CDS302 and CDS303
EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EN 61800-3, EN 61000-6-1/2,
1.1 (Full speed)
USB type B device plug
2
1-3 (break),1-2 (make)
240 V AC, 2 A
240 V AC, 0.2 A
60 V DC, 1 A
24 V DC, 0.1 A
4-6 (break), 4-5 (make)
400 V AC, 2 A
240 V AC, 0.2 A
80 V DC, 2 A
IP20, IP55
IP21, IP55
IP21/TYPE 1/IP 4X top
1.0 g
class 3C2
class 3C3
Max. 50 °C
0 °C
- 10 °C
-25 - +65/70 °C
1000 m
3000 m
159