Parameter Descriptions
Illustration 6.10
6
6
The parameters in this group allow selection of a
refrigerant, which implicitly determines the constants A1,
A2 and A3. Alternatively, user defined constants can be
programmed explicitly.
7-70 Refrigerant
Option:
[0]
R22
[1]
R134a
[2]
R404A
*
[3]
R407C
[4]
R410A
[5]
R502
[6]
R744
[7]
User defined
7-71 User Defined Refrigerant A1
Range:
[8.0000 –
12.0000]
7-72 User Defined Refrigerant A2
Range:
[-3000.00 –
-1500.00]
7-73 User Defined Refrigerant A3
Range:
[200.000 –
300.000]
76
Operating Instructions VLT
Function:
Function:
Selects the value used for the constant A1
in the pressure to temperature conversion
formula (see parameter group 7-7* Pressure
to Temperature Conversion).
Function:
Selects the value used for the constant A2
in the pressure to temperature conversion
formula (see parameter group 7-7* Pressure
to Temperature Conversion).
Function:
Selects the value used for the constant A3
in the pressure to temperature conversion
formula (see parameter group 7-7* Pressure
to Temperature Conversion).
®
MG34M302 - VLT
is a registered Danfoss trademark/Commercial Compressor
®
CDS302 and CDS303
6.8.4 7-8* Thermostat/Pressostat Function
The Thermostat-Pressostat Function (TPF) can be used to
stop and start the compressor when running in closed
loop. The TPF monitors and compares the resulting
feedback with the Cut-out value in 7-81 Cut-out Value.
When the resulting feedback gets below 7-81 Cut-out Value
a stop signal is generated and the compressor stops. When
the resulting feedback gets above the Cut-in value in
7-82 Cut-in Value the stop signal is removed and the
compressor starts again.
The Set-point should be set to a value in between Cut-in
and Cut-out.
Illustration 6.11
Point A: At start-up the temperature will be higher than
wanted in the evaporator and therefore a higher pressure
than the Cut-in level and the compressor must run.
Another situation could be that the start situation is where
the feedback is between Cut-out and Cut-in. In that case,
no STOP is initiated.