General Specifications
Mains Supply (L1, L2, L3)
Supply voltage
Supply voltage
Supply voltage
Supply frequency
Max. imbalance temporary between mains phases
True Power Factor (λ)
Displacement Power Factor (cos φ) near unity
Switching on input supply L1, L2, L3 (power-ups) ≤ 7.5 kW
Switching on input supply L1, L2, L3 (power-ups) ≥ 11 kW
Environment according to EN60664-1
The unit is suitable for use on a circuit capable of delivering not more than 100.000 RMS symmetrical Amperes, 240/500/600
V maximum
Motor Compressor Output (U, V, W)
Output voltage
Switching on output
Cable lengths and cross sections
Max. motor cable length, screened/armoured
Max. motor cable length, unscreened/unarmoured
Max. cross section to motor, mains, load sharing and brake *
Maximum cross section to control terminals, rigid wire
Maximum cross section to control terminals, flexible cable
Maximum cross section to control terminals, cable with enclosed core
Minimum cross section to control terminals
* See Mains Supply tables for more information!
Digital Inputs
Voltage level:
Voltage level, logic.0. PNP
Voltage level, logic.1. PNP
Voltage level, logic .0. NPN2)
Voltage level, logic .1. NPN2)
Maximum voltage on input
Input resistance, Ri
Safe Stop Terminal 37
Voltage level
Voltage level, logic.0. PNP
Voltage level, logic.1. PNP
Nominal input current at 24 V
Nominal input current at 20 V
Input capacitance
Terminal 37 is fixed PNP logic
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1.
Terminals 27 and 29 can also be programmed as output.
2.
Except safe stop input Terminal 37.
3.
Terminal 37 can only be used as safe stop input.
Terminal 37 is suitable for category 3 installations according to EN 954-1 (safe stop according to category 0 EN 60204-1) as
required by the EU Machinery Directive 98/37/EC. Terminal 37 and the Safe Stop function are designed in conformance with
EN 60204-1, EN 50178, EN 61800-2, EN 61800-3, and EN 954-1. For correct and safe use of the Safe Stop function follow the
related information and instructions in the Application Guidelines.
MG34M302 - VLT
®
Operating Instructions VLT
®
is a registered Danfoss trademark/Commercial Compressor
CDS302 and CDS303
3.0 % of rated supply voltage
≥ 0.9 nominal at rated load
Overvoltage category III/pollution degree 2
0-100% of supply voltage
See 14-01 Switching Frequency
2
1.5 mm
/16 AWG (2 x 0.75 mm
200-240 V ±10%
380-480 V ±10%
525-600 V ±10%
50/60 Hz
(> 0.98)
Max. 2 times/min.
Max. 1 time/min.
150 m
300 m
8
2
)
2
1 mm
/18 AWG
2
0.5 mm
/20 AWG
0.25 mm
2
0 - 24 V DC
< 5 V DC
> 10 V DC
> 19 V DC
< 14 V DC
28 V DC
approx. 4 kΩ
0 - 24 V DC
< 4 V DC
>20 V DC
50 mA rms
60 mA rms
400 nF
157