Parameter Descriptions
8-36 Max Response Delay
Range:
Size
related
10001 ms]
*
8-37 Max Inter-Char Delay
Range:
Size related
*
6.9.4 8-5* Digital/Bus
6
6
Parameters for configuring the control word Digital/Bus
merging.
NOTE
These parameters are active only when 8-01 Control Site is
set to [0] Digital and control word.
8-50 Coasting Select
Option:
[0]
Digital
input
[1]
Bus
[2]
Logic AND
[3]
Logic OR
*
8-51 Quick Stop Select
Select control of the Quick Stop function via the terminals
(digital input) and/or via the bus.
Option:
[0]
[1]
[2]
[3]
*
8-52 DC Brake Select
Option:
80
Function:
[
11. -
Specify the maximum permissible
delay time between transmitting a
request and receiving a response. If a
response from the frequency
converter is exceeding the time
setting then it will be discarded.
[ 0.00 - 35.00 ms]
Function:
Select control of the coasting function via the
terminals (digital input) and/or via the bus.
Activates Start command via a digital input.
Activates Start command via the serial
communication port or fieldbus option.
Activates Start command via the fieldbus/serial
communication port, AND additionally via one
of the digital inputs.
Activates Start command via the fieldbus/serial
communication port OR via one of the digital
inputs.
Function:
Digital input
Bus
Logic AND
Logic OR
Function:
Select control of the DC brake via the terminals
(digital input) and/or via the fieldbus.
MG34M302 - VLT
®
Operating Instructions VLT
CDS302 and CDS303
8-52 DC Brake Select
Option:
[0]
Digital
input
[1]
Bus
Function:
[2]
Logic AND Activates Start command via the fieldbus/serial
[3]
Logic OR
*
8-53 Start Select
Option:
[0]
Digital
input
[1]
Bus
[2]
Logic AND Activates Start command via the fieldbus/serial
[3]
Logic OR
*
8-54 Reversing Select
Option:
[0]
Digital
input
[1]
Bus
[2]
Logic AND
[3]
Logic OR
*
®
is a registered Danfoss trademark/Commercial Compressor
Function:
NOTE
Only selection [0] Digital input is available
when 1-10 Motor Construction is set to [1]
PM non-salient SPM.
Activates Start command via a digital input.
Activates Start command via the serial
communication port or fieldbus option.
communication port, AND additionally via one
of the digital inputs.
Activates Start command via the fieldbus/serial
communication port OR via one of the digital
inputs.
Function:
Select control of the frequency converter start
function via the terminals (digital input) and/or
via the fieldbus.
Activates Start command via a digital input.
Activates Start command via the serial
communication port or fieldbus option.
communication port, AND additionally via one
of the digital inputs.
Activates Start command via the fieldbus/serial
communication port OR via one of the digital
inputs.
Function:
Select control of the frequency converter
reverse function via the terminals (digital
input) and/or via the fieldbus.
Activates the Reverse command via the serial
communication port or fieldbus option.
Activates the Reverse command via the
fieldbus/serial communication port, AND
additionally via one of the digital inputs.
Activates the Reverse command via the
fieldbus/serial communication port OR via one
of the digital inputs.