Parameter Descriptions
4-55 Warning Reference High
Range:
999999.999
*
4-56 Warning Feedback Low
Range:
-999999.999
6
6
ReferenceFeed-
backUnit
*
4-57 Warning Feedback High
Range:
999999.999
ReferenceFeed-
backUnit
*
4-58 Missing Motor Phase Function
Displays alarm 30, 31 or 32 in the event of a missing motor
phase. It is strongly recommended to enable to avoid motor
damage.
Option:
[0]
[1]
NOTE
This parameter cannot be adjusted while the motor is
running.
58
Function:
[
par. 4-54 -
Enter the upper reference limit.
999999.999 ]
When the actual reference
exceeds this limit, the display
reads Ref High. The signal
outputs can be programmed to
produce a status signal on
terminal 27 or 29 and on relay
output 01 or 02.
Function:
[
-999999.999 -
Enter the lower
par. 4-57
feedback limit. When the
ReferenceFeed-
feedback falls below this
backUnit]
limit, the display reads
Feedb Low. The signal
outputs can be
programmed to produce
a status signal on
terminal 27 or 29 and
on relay output 01 or
02.
Function:
[
par. 4-56 -
Enter the upper
999999.999
feedback limit. When
ReferenceFeed-
the feedback exceeds
backUnit]
this limit, the display
reads Feedb High. The
signal outputs can be
programmed to produce
a status signal on
terminal 27 or 29 and
on relay output 01 or
02.
Function:
Off
No alarm is displayed if a
missing motor phase
occurs.
On
MG34M302 - VLT
®
Operating Instructions VLT
CDS302 and CDS303
6.5.3 4-6* Speed Bypass
Some systems call for avoiding certain output frequencies
or speeds, due to resonance problems in the system. A
maximum of four frequency or speed ranges can be
avoided.
4-60 Bypass Speed From [RPM]
Array [4]
Range:
Size related
4-61 Bypass Speed From [Hz]
Array [4]
Range:
Size related
4-62 Bypass Speed To [RPM]
Array [4]
Range:
Size related
4-63 Bypass Speed To [Hz]
Array [4]
Range:
Size related
®
is a registered Danfoss trademark/Commercial Compressor
Function:
[ 0 - par. 4-13
Some systems call for avoiding
*
RPM]
certain output speeds due to
resonance problems in the system.
Enter the lower limits of the
speeds to be avoided.
Function:
[
0.0 - par.
Some systems call for avoiding
*
4-14 Hz]
certain output speeds due to
resonance problems in the system.
Enter the lower limits of the speeds
to be avoided.
Function:
[ 0 - par. 4-13
Some systems call for avoiding
*
RPM]
certain output speeds due to
resonance problems in the system.
Enter the upper limits of the
speeds to be avoided.
Function:
[
0.0 - par.
Some systems call for avoiding
*
4-14 Hz]
certain output speeds due to
resonance problems in the system.
Enter the upper limits of the
speeds to be avoided.