Table 9. Input/Output Ratings And External Wiring Recommendations: Eaton 93Pm 50–80 Kw (400V) - Eaton 93PM Installation And Operation Manual

400v/480v four-wire 100 kw frame
Table of Contents

Advertisement

UPS Installation Plan and Unpacking
Table 9. Input/Output Ratings and External Wiring Recommendations: Eaton 93PM 50–80 kW (400V)
Basic Unit Rating
Input and Output Voltage
AC Input to UPS Rectifier (0.99 Minimum
pF) Full load current plus battery recharge
current, (3) Phases, (1) Ground
Minimum Conductor Size (Phase A, B, and C)
Number per Phase
Minimum Conductor Size (Ground)
Number
AC Input to UPS Bypass (Four-Wire, Dual-
Feed) – Full Load Current
(3) Phases, (1) Neutral – see Note, (1) Ground
Minimum Conductor Size (Phase A, B, C, and
Neutral)
Number per Phase
Minimum Conductor Size (Ground)
Number
DC Input from External Battery (Line-Up-
and-Match Eaton 93PM IBC) See Note
(1) Positive, (1) Negative, (1) Ground
Minimum Conductor Size (Phase Pos. and Neg.)
Number per Pole
Minimum Conductor Size (Ground)
Number
DC Input from External Battery (Standalone
Eaton 93PM IBC) See Note
(1) Positive, (1) Negative, (1) Ground
Minimum Conductor Size (Phase Pos. and Neg.)
Number per Pole
Minimum Conductor Size (Ground)
Number
AC Output to Critical Load (Four-Wire) –
Full Load Current
(3) Phases, (1) Neutral – see Note, (1) Ground
Minimum Conductor Size (Phase A, B, C, and
Neutral)
Number per Phase
30
Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04
Units
kW
50
Volts
400/400
Amps
93
A
AWG or kcmil
1
(1)
(each)
AWG or kcmil
6
(each)
(1)
Amps
93
B
AWG or kcmil
1/0
(1)
(each)
6
AWG or kcmil
(each)
(1)
Voltage
480
Total Amps
111
C
AWG or kcmil
2/0
(each)
(1)
See Note
4
AWG or kcmil
(each)
(1)
480
Voltage
Total Amps
111
C
AWG or kcmil
3/0
(2)
(each)
AWG or kcmil
4
(each)
(1)
Amps
72
D
2
AWG or kcmil
(1)
(each)
Rating 50/60 Hz
60
70
80
400/400
400/400
400/400
112
131
149
1/0
2/0
3/0
(1)
(1)
(1)
6
6
6
(1)
(1)
(1)
112
131
149
2/0
3/0
4/0
(1)
(1)
(1)
6
6
6
(1)
(1)
(1)
480
480
480
134
156
178
2/0
2/0
2/0
(1)
(1)
(1)
See Note
See Note
See Note
4
4
4
(1)
(1)
(1)
480
480
480
134
156
178
3/0
3/0
3/0
(2)
(2)
(2)
4
4
4
(1)
(1)
(1)
86
101
115
1
1/0
2/0
(1)
(1)
(1)