Eaton 93PM Installation And Operation Manual page 147

400v/480v four-wire 100 kw frame
Table of Contents

Advertisement

Load Compatibility
Overload Capability
1 1 0 0 . . 2 2 . . 3 3 U U P P S S E E n n v v i i r r o o n n m m e e n n t t a a l l
Operating Temperature
Operating Altitude
Storage Temperature
Relative Humidity (operating and
storage)
Acoustical Noise
Agency Markings
EMI Emissions and Immunity
Electrostatic Discharge (ESD)
Immunity
Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04
0.8 pF Leading
0.8 pF Lagging
<110% for 10 minutes
<125% for 60 seconds
<150% for 10 seconds
>150% for 300 milliseconds
5 to 40°C (41 to 104°F) without derating. The recommended operating temperature
is 25°C (77°F).
Maximum 1500m (5000 ft) at 40°C without derating
-25 to +55°C, excluding batteries (prolonged storage above 40°C causes rapid
battery self-discharge)
5 to 95%, noncondensing
100 kW at 100% load – 65 dBA at a 1m distance, per ISO 7779
UL 924 Emergency Lighting and Power Equipment
Safety: UL1778 5th Ed./CSA22.2 No. 107.3-14 3rd Ed.
Meets IEC 62040-2 C3 and FCC Part 15 Subpart B Class A, ICES-003, CISPR 22
Meets IEC 61000-4-2 Level 3 specifications. Withstands up to 4 kV contact pulse
without damage and with no disturbance or adverse effect to the critical load.