C C h h a a p p t t e e r r 3 3 U U P P S S I I n n s s t t a a l l l l a a t t i i o o n n P P l l a a n n a a n n d d U U n n p p a a c c k k i i n n g g
Use the following basic sequence of steps to install the UPS:
1.
Create an installation plan for the UPS system.
2.
Prepare your site for the UPS system.
3.
Inspect and unpack the UPS cabinet.
4.
Unload and install the UPS cabinet, and wire the system.
5.
Install features, accessories, or options, as applicable.
6.
Complete the Installation Checklist.
7.
Have authorized service personnel perform preliminary operational checks and start up the system.
3 3 . . 1 1
C C r r e e a a t t i i n n g g a a n n I I n n s s t t a a l l l l a a t t i i o o n n P P l l a a n n
Before installing the UPS system, read and understand how this manual applies to the system being installed.
Use the procedures and illustrations in paragraph
to create a logical plan for installing the system.
3 3 . . 2 2
P P r r e e p p a a r r i i n n g g t t h h e e S S i i t t e e
For the UPS system to operate at peak efficiency, the installation site should meet the environmental
parameters outlined in this manual. The operating environment must meet the weight, clearance, and
environmental requirements specified.
3 3 . . 2 2 . . 1 1 E E n n v v i i r r o o n n m m e e n n t t a a l l a a n n d d I I n n s s t t a a l l l l a a t t i i o o n n C C o o n n s s i i d d e e r r a a t t i i o o n n s s
The UPS system installation must meet the following guidelines:
The system must be installed on a level floor suitable for computer or electronic equipment.
The system must be operated at an altitude no higher than 1500m (5000 ft) without derating. For additional
assistance with high altitude operation, contact an Eaton service representative (see paragraph
1.9 Getting
The system must be installed in a temperature and humidity controlled indoor area free of conductive
contaminants.
Failure to follow guidelines may void your warranty.
The basic environmental requirements for operation of the UPS are:
Ambient Temperature Range: 5–40°C (41–104°F)
Recommended Operating Range: 5–40°C (41–104°F)
Maximum Relative Humidity: 5–95%, noncondensing
NOTE
Startup and operational checks must be performed by an authorized Eaton Customer
Service Engineer, or the warranty terms specified in
This service is offered as part of the sales contract for the UPS. Contact an Eaton service
representative in advance (a minimum two-week notice is required) to reserve a
preferred startup date.
Help).
Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04
Chapter 11 Warranty

3.2 Preparing the Site

and
become void.
Chapter 4 UPS System Installation
11