Eaton 93PM Installation And Operation Manual page 48

400v/480v four-wire 100 kw frame
Table of Contents

Advertisement

UPS Installation Plan and Unpacking
Table 15. Input/Output Ratings and External Wiring Recommendations: Eaton 93PM 60–100 kW (480V) (Continued)
DC Input from External Battery (Standalone
Eaton 93PM IBC)
(1) Positive, (1) Negative, (1) Ground
Minimum Conductor Size (Phase Positive and
Negative)
Number per Pole
Minimum Conductor Size (Ground)
Number
AC Output to Critical Load (Four-Wire) – Full
Load Current
(3) Phases, (1) Neutral – see Note, (1) Ground
Minimum Conductor Size (Phase A, B, and C, and
Neutral)
Number per Phase
Minimum Conductor Size (Ground)
Number
NOTE
Callout letters A, B, C and D map to the Oneline Schematics detailed in
Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM Integrated Battery Cabinet
(IBC).
The neutral conductor is sized the same as the phase conductor for balanced and resistive loads. Non-linear loads, up to
the maximum of 1.5x the load current, require a larger neutral conductor and should be sized in accordance with NFPA
NEC 70 Article 310.15(B)(5).
The power wiring terminals are pressure terminations, UL and CSA rated. See
cable terminations.
Figure 20
and
38
Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04
Figure 21
show the location of the UPS power cable terminals.
480
Voltage
Total Amps
134
C
3/0
AWG or kcmil
(each)
(2)
4
AWG or kcmil
(each)
(1)
Amps
72
D
1
AWG or kcmil
(1)
(each)
AWG or kcmil
6
(each)
(1)
Chapter 6 UPS Oneline
480
480
480
156
178
200
3/0
3/0
3/0
(2)
(2)
(2)
4
4
4
(1)
(1)
(1)
84
96
108
1/0
2/0
3/0
(1)
(1)
(1)
6
6
6
(1)
(1)
(1)
Schematics.
Table 16
for external power
480
223
3/0
(2)
4
(1)
120
4/0
(1)
6
(1)

Advertisement

Table of Contents
loading

This manual is also suitable for:

93pm series93pm-50-293pm-50-1

Table of Contents