Table 3-6. Input/Output Ratings And External Wiring Recommendations For The Eaton 93Pm-L 120 - (Single Input Bypass 220/208) - Eaton 93PM-L Installation And Operation Manual

20-120 kw (208v)
Hide thumbs Also See for 93PM-L:
Table of Contents

Advertisement

UPS Installation Plan and Unpacking

Table 3-6. Input/Output Ratings and External Wiring Recommendations for the Eaton 93PM-L 120 - (Single Input Bypass 220/208)

Basic Unit Rating
Input and Output Voltage
AC Input to UPS Bypass (Four Wire, Single-Feed)
Full Load Current: (3) Phases– see Note, (1) Ground
Neutral Current
Minimum Conductor Size (Phase A, B, and C)
Number per Phase
Neutral Wire Size
Number
Minimum Conductor Size (Ground)
Number
DC Input from External Battery (Line-Up-and-Match Eaton 93PM-L IBC-SW, IBC-LW or IBC-LHW)
For Line-Up-and-Match wiring refer to Eaton 93PM Integrated Battery Cabinet Installation Manual-Small Welded or Eaton 93PM Universal Integrated Battery
Cabinet Installation Manual-Large and Large High Rate
DC Input from External Battery (Standalone Eaton
93PM-L IBC)
(1) Positive, (1) Negative, (1) Ground
Minimum Conductor Size (Phase Positive and Negative)
Number per Pole
Minimum Conductor Size (Ground)
Number
AC Output to Critical Load (Four Wire)
Full Load Current
(3) Phases – see Note, (1) Ground
Neutral Current
Minimum Conductor Size (Phase A, B, and C, and Neutral)
Number per Phase
Neutral Wire Size
Number
Minimum Conductor Size (Ground)
Number
B, C
NOTE
Callout letters
and
NOTE
Line-up-and-match battery wiring with a 105°C
NOTE
The SAIC-B is sized for the maximum frame rating of 120 kW. For installations other than 120 kW, the SIAC-B breakers are considered as
switches and overcurrent protection must be provided by the upstream AC source breaker(s). For future upgradability, we recommend that
the system be wired to support the full UPS rating of 120 kW.
3-18
Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02
B
AWG or kcmil
AWG or kcmil
AWG or kcmil
C
AWG or kcmil
AWG or kcmil
D
AWG or kcmil
AWG or kcmil
AWG or kcmil
D
map to Figure 5-6 or Figure 5-7.
rating
is factory supplied with the Eaton 93PM-L Integrated Battery Cabinet (IBC).
Units
kW
20
40
Volts
220/208
220/208
Amps
67
134
Amps
96
192
1
250 MCM
(each)
(1)
(1)
2/0
500 MCM
(each)
(1)
(1)
6
(each)
(1)
(1)
Total Amps
45
90
6
(each)
(1)
(1)
8
(each)
(1)
(1)
Amps
56
111
Amps
96
192
3
3/0
(each)
(1)
(1)
2/0
500 MCM
(each)
(1)
(1)
8
(each)
(1)
(1)
Rating 50/60 Hz
60
80
220/208
220/208
202
269
288
385
500 MCM
250 MCM
(1)
(2)
300 MCM
500 MCM
(2)
(2)
2
1/0
2
(1)
(2)
136
181
2
2/0
4/0
(1)
(1)
8
4
2
(1)
(1)
167
222
288
385
350 MCM
3/0
(1)
(2)
300 MCM
500 MCM
(2)
(2)
4
2
4
(1)
(2)
www.eaton.com/powerquality
100
120
(See Note)
220/208
220/208
336
403
481
577
350 MCM
500 MCM
(2)
(2)
4/0
300 MCM
(4)
(4)
2
1/0
(2)
(2)
226
271
300 MCM
350 MCM
(1)
(1)
2
2
(1)
(1)
278
333
481
577
250 MCM
350 MCM
(2)
(2)
4/0
300 MCM
(4)
(4)
2
2
(2)
(2)