Display Menu Operation; System Events - Eaton 93PM Installation And Operation Manual

400v/480v four-wire 100 kw frame
Table of Contents

Advertisement

Table 31. Status Indicators
Indicator
Status
On
Green
Off
On
Yellow
On
Yellow
On
Red
Flashing
7 7 . . 2 2 . . 2 2 S S y y s s t t e e m m E E v v e e n n t t s s
When the UPS system is running in Double Conversion mode, it continually monitors itself and the incoming
utility power. In Battery or Bypass modes, the UPS may issue alarms to let you know exactly what event
caused the change from Double Conversion mode. System events on the UPS can be indicated by horns,
lights, messages, or all three.
Select the LOGS tab from the navigation bar on main menu screen to display the active events screen. This
screen shows any currently active alarms, notices, or commands. For more information on using the events
screen, see paragraph
7.2.6 Display Menu
System Event Horns – The system event horn beeps to alert an operator that an event needing attention
is taking place. The horn cycles at a half-second rate. To silence the horn, touch any control panel button.
System Event Indicators – The status indicators on the UPS control panel work with the event horn to let
the operator know when the UPS is operating in any mode other than double conversion. Only the normal
mode indicator is illuminated during normal UPS system operation. The other indicators illuminate to
indicate alarms or events. When an alarm occurs, first check these indicators to see what type of event
has taken place. For descriptions of the status indicators, see paragraph
System Event Messages – When a system event occurs, a message appears on the LCD in the UPS
status area. This message is also written to the Events Log and may be added to the History Log. The
messages are divided into four categories: alarms, notices, status, and commands.
Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04
Description
The UPS is in Double Conversion mode. The power module is supplying power to the
critical load.
The UPS is turned off.
The UPS is in Battery mode. Because Battery mode is a normal condition of the UPS, the
normal indicator also remains illuminated.
The UPS is in Bypass mode. The critical load is supported by the bypass source. The normal
indicator is not illuminated when the system is in Bypass mode.
The UPS has an active alarm and requires immediate attention. The LCD shows the highest
priority active alarms. All alarms are accompanied by an audible horn. To silence the horn,
touch any control panel button. The Alarm indicator may be illuminated along with other
indicators.
There is a new UPS alarm condition. The indicator flashes until acknowledged by touching
any control panel button once.
Operation.
UPS Operating Instructions
7.2.1 Status
Indicators.
99

Advertisement

Table of Contents
loading

This manual is also suitable for:

93pm series93pm-50-293pm-50-1

Table of Contents