UPS Installation Plan and Unpacking
•
External parallel system wiring length should be in accordance with
equal current sharing when in bypass mode.
Figure 11. 93PM External Parallel Wire Length
NOTE Required parallel system wiring length must be equal to ensure approximately equal current
sharing when in Bypass mode. For proper operation the following must be true:
NOTE Any difference in wire length will result in decreased capacity of the UPS system while on
bypass. For example, a 10% difference between the longest and shortest wire lengths will result
in a decrease in bypass capacity of 10%.
For external wiring recommendations, including the minimum AWG size of external wiring, see
through
This product has been evaluated for use with copper wire only. For external wiring, use only 75°C copper wire.
24
Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04
Bypass Input to
UPS Units
1A
2A
3A
4A
1A = 2A = 3A = 4A
1B = 2B = 3B = 4B
Table
15. Wire sizes listed are for copper wiring only.