Eaton 93E Generation 2 UPS 100-200 kVA
(380/400/415V)
Figure 37. Main menu and the Mimic screen
7.2.6
21
Table
Note: The UPS is not a measuring device. All displayed measurements on the
meter screen are only approximate values.
Table 21: Display menu operation
Function
Meters –
UPS
©
Eaton Corporation plc 2019. All rights reserved.

Display menu operation

describes the menu functions and how to use them.
Sub-func-
Operation
tion
The Meters screens show the UPS meter readings for the
unit. The default voltage displayed on these screens is phase-
to-neutral. These can be changed to display the voltage
phase-to-phase (A-B, B-C, C-A). Use the
tons to select the METERS symbol on the main menu bar to
display the Meter screens. To scroll through the Meter
screens, press the
readings are displayed in the information area of the screen.
Output –
The Output screen shows the output voltage (phase to neu-
UPS
tral), output current (each phase), and frequency being sup-
plied by the UPS, as well as the kVA, kW, and power factor
measurements.
Input –
The Input screen shows the input voltage (phase to neutral),
UPS
input current (each phase), and frequency of the incoming
utility source, as well as the kVA, kW, and power factor meas-
urements.
Bypass
The Bypass screen shows the bypass input voltage (phase to
neutral), input current (each phase), and frequency of the in-
coming utility source, as well as the kVA, kW, and power fac-
tor measurements.
Battery –
The Battery screen displays the battery voltage (Vdc), the
UPS
battery current (Idc) and battery time remaining (BTR).
or
push button. The current UPS
Revision: 002
Document ID: P-164000848
User's and installation guide
or
push but-
82 (118)