5. Conversion and maintenance
5.3.7 Conversion of the left−hand end plate of IP40 on IP65 cover
Dismantling IP40 cover
Mounting of IP65 cover
5.3.8 Conversion of the outlet direction of the multi−pin cable
Festo P.BE−MPAL−EN en 1008NH
The procedure for the conversion of pressure zones
corresponds to the exchange or extension of components,
as described in Chapter 5.3.2.
Applies only to the versions with 25−/44 pin Sub−D multi−pin
plug connection.
Proceed as follows:
1. Loosen and remove both locking rings on the Sub−D plug.
2. Loosen and remove the four screws of the IP40 cover.
3. Remove the IP40 cover.
Proceed as follows:
1. Check that the seal is not twisted in the slot of the cover.
2. Place the cover as far as possible at right angles on the
multipin sub−base, so as not to damage the contacts of
the Sub−D plug.
3. Secure the cover to the left−hand end plate with the four
screws provided (Torx, size 10, torque 1.2 Nm ±10%).
4. Connect the electrical cables according to the short
description provided with the product.
Applies only to the versions of the valve terminal MPA−L with
multi−pin connection and IP65 cover.
5−19