Conversion Between Internal And External Pilot Air Supply - Festo MPA-L Series Description

Valve terminal
Table of Contents

Advertisement

5. Conversion and maintenance

5.3.5 Conversion between internal and external pilot air supply

5−16
2. Secure the flat plate silencer and the cover plate with the
four original screws. Tighten them to 1.4 Nm ±10%.
Proceed as follows to convert to ducted exhaust air:
1. Loosen the 4 attachment screws of the co ver plate and
remove the cover plate and the flat plate silencer from the
supply plate.
2. Locate the seal supplied with the exhaust plate in the slot
between the supply plate and the exhaust plate.
3. Fasten the exhaust plate only with the four original
screws. Tighten them to 1 Nm ±10%.
Right−hand end plate with lateral ports
Connections (3) and (5) can be fitted optionally with silencers
or with connections for tubing lines.
Note
Mixed operation of the valve terminal MPA−L with internal
and external pilot air is not intended. Independently of the
available pressure zones for various operating pressures
all solenoid coils of the valve terminal MPA−L are supplied
with a common pilot air supply.
The pilot air supply that your valve terminal MPA−L is set for
can be determined from the position of the selector plate (see
Chapter 1.5.3).
Festo P.BE−MPAL−EN en 1008NH