Structure Of The Slave Diagnostic Data - Siemens SIMATIC VS130 Series Manual

Vision sensor
Table of Contents

Advertisement

Diagnostics
Its local variables OB_82_EV_CLASS, OB_82_MDL_DEFECT, and
OB82_EXT_FAULT can have the following values:
Variable
OB_82_EV_CLASS
OB_82_MDL_DEFECT
OB_82_EXT_FAULT
The entry "Module OK" now appears in the diagnostic buffer and the error text from
the GSD file is no longer shown as the module status of the VS 130.
7.4.3

Structure of the Slave Diagnostic Data

PROFIBUS
Frame
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
Byte 9
Byte 10
7-8
Value
B#16#38
FALSE
FALSE
Meaning
Station status1 (bit 3 = 1:
external diagnostic data
exists)
Station status 2
Station status 3
Master PROFIBUS address
Vendor ID (high byte):
B#16#81
Vendor ID (low byte):
B#16#00
Length of the VS 130-specific
diagnostic data incl. byte 6:
B#16#05
Diagnostic byte 0 (bit 1
"Sensor not found")
Diagnostic byte 1
Diagnostic byte 2
Diagnostic byte 3
Meaning
Event exiting state
No module fault
No external error
Range of Validity
According to standard
According to standard
According to standard
According to standard
According to standard
According to standard
According to standard
VS 130-specific
VS 130-specific
VS 130-specific
VS 130-specific
Vision Sensor VS 130