Technical data

6.1

Power

• Standard: 10 ... 30 V DC, 60 mA max.
• IS: 5 ... 16 V DC, 25 mA max. (from IS Switch Isolator)
6.2

Ambient temperature

• Standard: -40 ... +55 °C (-40 ... +131 °F)
• IS: -25 ... +55 °C (-13 ... +131 °F)
6.3

Inputs

• Shaft rotation 0.5 ... 2 000 rpm, bi-directional, resolution dependent
6.4

Outputs

• Uni-directional open collector sinking output
• Standard: 10 ... 30 V DC, 25 mA max.
• IS: load current, 0 ... 15 mA
• 32, 256, 1 000, or 2 000 pulses per revolution (PPR)
PPR
32
256
1 000
2 000
Max. RPM limited to 1000 for use in Intrinsically safe/mining applications.
1)
6.5

Construction

Enclosure
• Aluminum, rated NEMA 4X/Type 4X/IP65
• Stainless steel (optional), rated NEMA 4X/Type 4X/IP65
SITRANS WS300
Operating Instructions, 08/2020, A5E45050935-AB
Max. RPM
2 000
1)
2 000
1)
900
450
1)
Hz
1 066
8 530
15 000
15 000
6
27