IC-KP-B7-V95
Commissioning
6.4
Output of the contents of read data carriers on the display
In the first menu level, the IDENTControl shows the contents of read data carriers
on the display. Information messages of this kind are marked with a bell icon (
in the top right corner of the display to distinguish them from menu items.
A maximum of the first 12 characters of the read data set can be displayed. The
following characters may be excluded.
The view on the display can be toggled by pressing the arrow buttons. The
following display variants are available:
Note!
Data carrier content from commands that are activated manually on the
IDENTControl are always displayed, irrespective of the menu level that was just
displayed.
6.5
Setting the network parameters
The following parameters must be set manually via the display:
Caution!
Always use parameters that you know are compatible with your network.
Setting parameters
To set the parameters using the function buttons, proceed as follows:
1. Press return (confirm input).
2. Select IDENT gateway (down arrow button, return).
3. Press return to confirm the option Address ...
4. Enter the bus address using the arrow buttons.
5. Press return to save and exit the menu item.
6. Proceed with the options Baud rate, Assembly instance and Data hold time in
7. Initiate a reset (menu) or disconnect the power supply to restart the device.
22
HEX (hexadecimal with decimal delimiter)
■
HEX2 (hexadecimal without decimal delimiter)
■
ASCII (ASC)
■
Bus address
■
Baud rate
■
Assembly instance
■
Data hold time
■
the same way.
The settings only take effect after the reset.
)