Example 2 - Pepperl+Fuchs IC-KP-B7-V95 Manual

Identcontrol interface with devicenet interface
Table of Contents

Advertisement

IC-KP-B7-V95
Appendix A
A response appears in the input field:
Byte no.
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
Byte 9
Byte 10
Byte 11
1. only IPC02 and IPC11
11.2

Example 2

Assembly objects 104d/154d (separated mode) are used in the example. The
following functions are activated:
The following prerequisites must be fulfilled:
Setting the connection parameters
Configure the parameters on the PLC as follows:
Assembly instance
Input: 154
Output: 104
Configuration: 112
(this value is used for all input/output
instances)
Use
Command code
Channel/Toggle bit
Status
Reply counter
ID code 00h ... FFh
ID code 00h ... FFh
ID code 00h ... FFh
ID code 00h ... FFh
ID code 00h ... FFh
Set tag type IPC03 on channel 1 and channel 2.
Write data to a IPC03 tag.
Read data from a IPC03 tag.
One type IPH-XX R/W head is connected to channel 1 and channel 2 on
the IDENT Control.
One type IPC03 data carrier is located in front of each R/W head.
The MAC address on the IDENTControl is set to '01' (see chapter 6.5).
The device is connected to the network.
Contents Description
01h
Command SF (Single read read
only code)
06h
Channel = 3
Toggle bit = 0
00h
Command executed.
08h
For every IDENT telegram, the
value on the reply counter
increases by 1.
-
<ID code>
-
<ID code>
-
<ID code>
-
<ID code>
-
1
<ID code>
00h
00h
00h
Size (32 bits)
8
8
0
(this value is used for all input/output
instances)
77