IC-KP-B7-V95
Installation
5.4.5

DeviceNet connection guide

Network connection
The network connection is established using a DeviceNet MiniStyle connector.
The pin assignment is taken from the drawing below.
4
5
1
2
3
4
5
Connecting cable
The device must always be connected using the "Thick" and "Thin" extension
cables described in the DeviceNet specification. Refer to the "Thick cable profile"
and "Thin cable profile" sections in the DeviceNet specification for more detailed
information.
Transfer rates and cable lengths
Baud rate
125 kBits/s
250 kBits/s
500 kBits/s
18
3
2
1
Ground / uncoated
V+ / RD
V- / BK
CAN_H / WH
CAN_L / BU
Max. length of the transfer cable
500 m
250 m
100 m