UPS5000-A-(200 kVA-800 kVA)
User Manual
Figure 5-8 Logging in to the WebUI
Step 5 On the home page of the WebUI, choose Monitoring > Control, click Inv. ON, and confirm
the operation to start the inverter.
Figure 5-9 Starting the inverter
----End

5.1.3 Powering On Loads

Context
After the inverter starts, the UPS works in normal mode. The Bypass mode alarm disappears.
Procedure
Step 1 After confirming that the battery strings are properly connected, close the battery string input
circuit breaker. If there are multiple battery strings, close the circuit breaker for each battery
Issue 03 (2019-02-15)
If the power unit receives a startup command when it cannot be started, the startup command will be
kept for 1 minute. If the startup command is not cleared within 1 minute (for example, other faults occur
on the unit, or you perform shutdown or rectify faults) and the unit can be started, the unit responds to
the startup command.