Huawei UPS5000-A-300K-STT User Manual page 246

200 kva-800 kva
Hide thumbs Also See for UPS5000-A-300K-STT:
Table of Contents

Advertisement

UPS5000-A-(200 kVA-800 kVA)
User Manual
Item
D.G. power
limiting (kVA)
D.G. charger
power ratio (%)
Input cur.
limiting
Input cur.
limiting ratio
(%)
Output Settings
Figure 4-22 Output settings
Item
Output voltage
level
Issue 03 (2019-02-15)
Description
Set these two parameters to
control the valid input current
and limiting input current, which
prevents load impact and
facilitates better cooperation
between the UPS and the D.G.
Specifies whether to enable or
disable input current limiting to
protect generators.
Limits the input current to protect
the D.G.
Description
Specifies the system output
voltage level. This parameter is
configurable only after the
inverter shuts down. After you
change the voltage level, the
upper limit of the bypass voltage
restores to the default value. (If
the voltage level is 380 V or 400
V, the default upper limit is
+15%. If the voltage level is 415
V, the default upper limit is
+10%.)
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
Depends on the
0 kVA to 5000
actual model.
kVA
0
0%–100%
Disable
Disable, Enable
200%
50%–200%
Default Value
Value Range
400
380, 400, 415
237