UPS5000-A-800 kVA Quick Guide
Issue: 04
Part Number: 31508416
Date: 2019-03-02
1
Overview
Model
Configuration
Weight
Dimensions (H x W x D)
Power
Power
cabinet
cabinet
Copyright © Huawei Technologies Co., Ltd. 2019. All rights reserved.
UPS5000-A-800K-F800-SC
Standard configuration
1530 kg
2000 mm x 2400 mm x 850 mm
Bypass
Bypass
cabinet
cabinet
1
UPS5000-A-800K-F800-FC
Full configuration
1610 kg
(1) Power unit
(2) Control unit
(3) Mains input switch (only available
in the full configuration model)
(4) Maintenance bypass switch
(5) Output switch (only available in the
full configuration model)
(6) Bypass unit
(7) Bypass input switch (only available
in the full configuration model)

Advertisement

Table of Contents
loading

Summary of Contents for Huawei UPS5000-A-800 Series

  • Page 1 UPS5000-A-800 kVA Quick Guide Issue: 04 Part Number: 31508416 Date: 2019-03-02 Copyright © Huawei Technologies Co., Ltd. 2019. All rights reserved. Overview Model UPS5000-A-800K-F800-SC UPS5000-A-800K-F800-FC Configuration Standard configuration Full configuration Weight 1530 kg 1610 kg Dimensions (H x W x D)
  • Page 2: Installing The Ups

    2. Use insulated tools during installation. 3. Only engineers certified by Huawei or its agents are allowed to install, commission, and maintain the UPS. Otherwise, personal injury or equipment damage may occur, and the UPS faults caused are beyond the warranty scope of Huawei.
  • Page 3 2. Secure the UPS. (A) Mounting holes on the steel channel: M12x60 bolts (B) Mounting holes on the floor: M12x100 expansion bolts Bolts are not included. 3. Install anchor baffle plates. 4. Remove the front cover and No. 10 protection panel from the bypass cabinet and the filler panel from the power cabinet.
  • Page 4: Connecting Cables

    5. Cut off the cable ties bound between holes of copper bars No. 23, 24, 25, 26, and 30. Install soft copper bars in the bypass cabinet and its adjacent power cabinet from inside out. Then, install soft copper bars No. 52. 6.
  • Page 5 The cabling route is for reference only. Connect cables based on site requirements. Connecting Signal Cables to Combined Cabinets NOTE A UPS in standard configuration has only one switch cable (maintenance bypass switch). A UPS in full configuration has three switch cables (mains input switch, maintenance bypass switch, and bypass input switch).
  • Page 6 Port Silk Screen on the Power Bypass Cabinet Bypass Cabinet Cable Label or Cabinet Parallel Board or Cable Cable Name Number Number W301_J21 Bypass unit DL37 cable W303_J24 ECM 8-pin cable W305_J22 ECM system W307_J25 monitoring bus CT cable W309_J26 ...
  • Page 7 3. Connect the ground cable, power cables, and signal cable. Signal cable Mains input power cable Battery cable Output power cable Ground cable Bypass input power cable (no need to connect in case of only one mains input)  The mains input and bypass input share the N busbar.
  • Page 8 Scenario 2: Routing Cables from the Bottom 1. Remove the cable covers from the bottom of the cabinet, drill holes in the covers, attach grommet strips to the hole edges to protect the cables, and reinstall the cable covers. 2. (Skip this step if the mains input and bypass input share a power source.) Remove the copper bars between the mains input and bypass input.
  • Page 9: Verifying The Installation

    Verifying the Installation 1. Check that there is no foreign matter at the top and bottom of the cabinets, copper bars, switches, and the rear of units. Rear view Front view 2. After verifying the installation, reinstall all 4. Do not remove the dustproof cover before the covers.
  • Page 10: Powering On The Ups

    Close the upstream bypass and mains input switches. (Full configuration model) Close the UPS bypass input switch, output switch, and mains input switch. After the UPS is powered on, initialization begins. The MDU displays the Huawei logo and an initialization progress bar.
  • Page 11 b) After you set parameters on the Settings Wizard screen, the MDU displays the Bypass mode and No battery alarms, which do not need to be handled. If there is any other alarm, you need to rectify the fault. c) View the system running status diagram on the MDU to check that the UPS is working in bypass mode.
  • Page 12: Shutting Down The Ups

    Powering On Loads 1. After the inverter starts, the UPS works in normal mode. The Bypass mode alarm disappears from the MDU. 2. After confirming that the battery strings are properly connected, turn on the battery string input circuit breaker. If there are multiple battery strings, turn on the circuit breaker for each battery string and then turn on the general circuit breaker between battery strings and the UPS.
  • Page 13 Keep the dowel level, insert the switch extension rod to the marked position, place washers properly, and tighten the slotted screw to install the switch extension rod. Huawei Technologies Co., Ltd. Huawei Industrial Base, Bantian, Longgang Shenzhen 518129 People's Republic of China www.huawei.com...