UPS5000-A-(200 kVA-800 kVA)
User Manual
The currents listed in the following table are measured at the rated voltage of 380 V.
Table 3-9 Recommended cross-sectional areas for power cables
Item
Main
Input current (A)
s
Recomme
input
nded
cross-secti
onal area
2
(mm
)
Bypa
Input current (A)
ss
Recomme
input
nded
cross-secti
onal area
2
(mm
)
Outp
Output current (A)
ut
Recomme
nded
cross-secti
onal area
2
(mm
)
Batte
Nominal battery
ry
discharge current
input
(A)
Maximum battery
discharge current
(A)
Recomme
nded
cross-secti
Issue 03 (2019-02-15)
The UPS can generate large leakage currents. A circuit breaker equipped with an RCD is
not recommended.
If multiple UPSs are connected in parallel, input and output power cables for each UPS
should have the same length and specifications.
300K-FT
533
L1
2 x (4 x 150)
L2
L3
N
PE
150
456
L1
2 x (4 x 150)
L2
L3
N
PE
150
456
U
2 x (4 x 150)
V
W
N
PE
150
658
788
+
2 x (3 x 185)
N
Copyright © Huawei Technologies Co., Ltd.
400K
500K
711
889
2 x (4 x 240)
3 x (4 x 185)
240
240
608
760
2 x (4 x 240)
3 x (4 x 185)
240
240
608
760
2 x (4 x 240)
3 x (4 x 185)
240
240
877
1096
1051
1313
2 x (3 x 240)
3 x (3 x 185)
3 Installation
600K
800K
1066
1422
4 x (4 x 185)
4 x (4 x 240)
240
240
912
1215
4 x (4 x 185)
4 x (4 x 240)
240
240
912
1215
4 x (4 x 185)
4 x (4 x 240)
240
240
1316
1754
1576
2101
3 x (3 x 240)
4 x (3 x 240)
63