Shut down the UPS inverter. Shut down the inverter on the LCD or WebUI, and the UPS
transfers to bypass mode.

5.5 Setting ECO Mode

Prerequisites
The system is working in inverter mode.
Context
Procedure
Step 1 On the LCD of the system, choose System Info > System Settings and set Working mode to
ECO. The information indicating that the UPS works in ECO mode is displayed on the LCD.
Step 2 Set the ECO voltage range.
Figure 5-13 ECO parameters
Step 3 If you set ECO mode in bypass mode, manually start the UPS inverter.
Issue 03 (2019-02-15)
If the inverter is shut down when the input voltage or frequency exceeds the specified threshold, the
UPS supplies no power, and the loads shut down.
The UPS is set to non-ECO mode by default. Set the UPS to ECO mode when energy
saving is required.
In ECO mode, the bypass takes priority over the inverter in supplying power. If the
bypass is disconnected, the UPS transfers to normal mode.
To avoid frequent transfer between ECO mode and normal mode, do not set the ECO
mode when the bypass input is unstable or is sensitive to load changes.
ECO mode is not recommended when the load is less than 10%.
Before transferring the UPS to ECO mode, ensure that the bypass unit works properly.