Figure 4-26 Battery settings 3
Item
Battery type
Single battery
voltage (V)
Single battery
capacity (Ah)
Batteries in a
battery string
Number of
battery strings
Installation
time
Maintenance
period (d)
Chg. cur.
limiting coef.
(C10)
Cell float
voltage (V/cell)
Cell equalized
volt. (V/cell)
Dis. cur. 0.1C
EOD (V/cell)
Issue 03 (2019-02-15)
Description
Currently, only VRLA batt. is
supported.
Specifies the voltage of each
battery that is connected in the
battery string in series.
Specifies the capacity of each
battery that is connected in the
battery string in series.
Specifies the number of batteries
in a battery string.
Specifies the number of battery
strings connected in parallel.
A battery maintenance reminder
is displayed when the
maintenance time (counted from
the installation time) comes.
Specifies the interval for
reminding users of battery
maintenance.
The charging current limit is a
multiple of the battery capacity.
Specifies the battery float
charging voltage.
Specifies the battery equalized
charging voltage.
Specifies the EOD threshold
when the discharging current is
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
-
-
12 V
2, 6, 12
Depends on the
5–9999
actual model.
The default
The value range
value depends
depends on the
on the model.
model.
1
1–4
-
-
0
0–365
0.1C10
0.05C10 to
0.15C10
2.23 V/cell to
2.25 V/cell
2.30 V/cell
2.35 V/cell
2.30 V/cell to
2.40 V/cell
1.80 V/cell
1.8–1.9
241