Huawei UPS5000-A-300K-STT User Manual page 269

200 kva-800 kva
Hide thumbs Also See for UPS5000-A-300K-STT:
Table of Contents

Advertisement

UPS5000-A-(200 kVA-800 kVA)
User Manual
Item
Float Chg
Temp Comp
Center (° C)
Automatic
equalized
charging
Transfer-to-equ
alized charging
cur. coef. (C10)
SOC to start
equalized
charging (%)
Scheduled
equalized
charging
interval (d)
Equalized
charging
protection
interval (d)
Forced
equalized
charging
protection time
(h)
Issue 03 (2019-02-15)
Description
Indicates the reference
temperature during temperature
compensation of the float
charging voltage.
If this parameter is set to Enable,
the UPS automatically changes
the battery management status to
equalized charge based on the
charge current and float charge
time.
The battery enters equalized
charge state when the battery
current exceeds this parameter
value.
If the SOC is lower than the
specified value, batteries start
equalized charging.
After batteries transfer from
equalized charging to float
charging, if the batteries do not
discharge, equalized charging
starts only after the float charging
time reaches Equalized
charging protection interval.
After equalized charging is
complete, scheduled equalized
charging starts when the
non-equalized charging time
exceeds Scheduled equalized
charging interval.
When batteries are continuously
under float charging or
hibernation, enable forced
equalized charging. When the
forced equalized charging time
reaches the value of this
parameter, batteries
automatically transfer to float
charging mode.
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
25
20–30
Enable
Disable, Enable
0.05
0.02–0.08
70
0–100
60
30–180
7
0–15
18
12–24
260