UPS5000-A-(200 kVA-800 kVA)
User Manual
Item
Output volt.
adjustment (V)
Output
frequency (Hz)
Output freq.
track rate
(Hz/s)
Bypass Settings
Figure 4-23 Bypass settings
Item
Issue 03 (2019-02-15)
Description
The output voltage can be
slightly adjusted based on the
onsite power distribution
condition to ensure a minimum
difference between the output
voltage and the bypass voltage
and facilitate uninterruptible
power supply when the UPS
transfers from normal mode to
bypass mode.
Specifies the system output
frequency level.
This parameter can be adjusted
based on site requirements. If
Output freq. track rate (Hz/s)
is slow, the inverter frequency is
different from the bypass
frequency when the bypass
frequency changes. If output is
overloaded or the inverter is
faulty, an interruption (less than
20 ms) occurs when the UPS
transfers from normal mode to
bypass mode. If Output freq.
track rate (Hz/s) is fast, the
inverter frequency is unstable.
Description
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
The default
380 V:
value is 220.0,
209.0–231.0
230.0, and 240.0
400 V:
when the
218.5–241.5
voltage level is
415 V:
380 V, 400 V,
228.0–252.0
and 415 V
respectively.
50 Hz
50 Hz, 60 Hz
0.6 Hz/s
0.1 Hz/s to 2.0
Hz/s
Default Value
Value Range