Huawei UPS5000-A-300K-STT User Manual page 245

200 kva-800 kva
Hide thumbs Also See for UPS5000-A-300K-STT:
Table of Contents

Advertisement

UPS5000-A-(200 kVA-800 kVA)
User Manual
Item
Inter-rack
power unit start
delay (s)
NTC
BCB trips if
UPS stops
power supply
Input Settings
Figure 4-21 Input settings
Item
D.G. mode
Issue 03 (2019-02-15)
Description
Intra-rack power unit start
delay (s) can be set to a value
ranging from 0.5 to 120.
Inter-rack power unit start
delay (s) can be set to a value
ranging from 2 to 120. The preset
value of Inter-rack power unit
start delay (s) is 5.0. The start
delay of a unit in a rack varies
depending on the rack number
and unit number. #1 unit in rack
1 does not have a start delay.
The short-distance battery
temperature sensor monitors the
ambient temperature near
batteries, and ensures that
batteries work reliably and
securely.
N/A
Description
Set this parameter to Enable
when a D.G. connects to the
input PDC. The UPS enters the
D.G. mode when a D.G. is
detected over dry contacts.
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
5
2–120
Disable
Disable, Enable
Enable
Disable, Enable
Default Value
Value Range
Disable
Disable, Enable
236