UPS5000-A-(200 kVA-800 kVA)
User Manual
Table 3-5 Power cable terminal requirements for the UPS5000-A-200K-ST
Port
Descript
ion
Mains
input
Bypass
input
Battery
input
Output
PE
Table 3-6 Power cable terminal requirements for the UPS5000-A-200K-FT
Port
Descript
ion
Mains
input
Bypass
input
Battery
input
Output
PE
Issue 03 (2019-02-15)
The ambient temperature is 30° C.
The AC voltage loss is less than 3%, and the DC voltage loss is less than 1%.
200 kVA: single- or multi-core 90° C flexible power cable with a copper conductor;
300 kVA: single-core 90° C flexible power cable with a copper conductor.
Recommended cable lengths: for a 200 kVA UPS, AC power cable ≤ 30 m, DC
power cable ≤ 40 m; for a 300 kVA UPS, AC power cable ≤ 30 m, DC power cable
≤ 50 m.
Connection
Method
Crimped OT
terminal
Crimped OT
terminal
Crimped OT
terminal
Crimped OT
terminal
Crimped OT
terminal
Connection
Method
Crimped OT
terminal
Crimped OT
terminal
Crimped OT
terminal
Crimped OT
terminal
Crimped OT
terminal
Copyright © Huawei Technologies Co., Ltd.
Bolt
Bolt Hole
Specificat
Diameter
ions
M10
10.5 mm
M10
10.5 mm
M12
13.5 mm
M10
10.5 mm
M10
10.5 mm
Bolt
Bolt Hole
Specificat
Diameter
ions
M10
10.5 mm
M10
10.5 mm
M12
13.5 mm
M10
10.5 mm
M10
10.5 mm
3 Installation
Bolt Length
Torque
30 mm
26 N· m
30 mm
26 N· m
45 mm
46 N· m
30 mm
26 N· m
30 mm
26 N· m
Bolt Length
Torque
40 mm
26 N· m
40 mm
26 N· m
60 mm
46 N· m
40 mm
26 N· m
30 mm
26 N· m