UPS5000-A-(200 kVA-800 kVA)
User Manual
8.1 Physical Parameters
Item
Protection level
Communication
8.2 Internal Switch Parameters
UPS
UPS5000-A-20
0K-ST
UPS5000-A-20
0K-FT
UPS5000-A-30
0KTTL
UPS5000-A-30
0K-STT
UPS5000-A-30
0K-FT
UPS5000-A-40
0K-SC
Issue 03 (2019-02-15)
8
Technical Specifications
Specifications
IP20 (IP21 can be reached by configuring IP21 components.)
NOTE
IP21 components cannot be configured for the UPS5000-A-300K-STT or
UPS5000-A-200K-FT.
Supports dry contacts, RS485 ports, and FE ports. Supports Simple
Network Management Protocol (SNMP).
Maintenance
Bypass
Switch
1000 V AC/400
A/3P
690 V AC/400
A/3P
1000 V AC/630
A/3P
1000 V AC/630
A/3P
1000 V AC/630
A/3P
1000 V AC/630
A/3P
Copyright © Huawei Technologies Co., Ltd.
Mains Input
Bypass Input
Switch
Switch
-
-
690 V AC/400
690 V AC/400
A/3P
A/3P
-
-
-
-
1000 V AC/800
1000 V AC/630
A/3P
A/3P
-
-
8 Technical Specifications
Output
Switch
-
690 V AC/400
A/3P
-
-
1000 V AC/630
A/3P
-
318