8.9 System Electrical Specifications

Item
Redundancy design
ECO
Issue 03 (2019-02-15)
Specifications
In normal mode, the mains frequency is synchronous with the
bypass input frequency.
In battery mode, the frequency is 50 Hz/60 Hz with a tolerance of
± 0.05%.
< 1% (full linear load)
< 4% (full non-linear load)
1
0 ms
Voltage unbalance: ± 3%; phase unbalance: ± 2°
Inverter overload capability:
100% < load ≤ 110%: transfer to bypass mode after 60 min
110% < load ≤ 125%: transfer to bypass mode after 10 min
125% < load ≤ 150%: transfer to bypass mode after 1 min
Load > 150% or a short circuit occurs: run for 200 ms
Copyright © Huawei Technologies Co., Ltd.
Specifications
Control units and parallel signals use a
redundancy design.
Supported
8 Technical Specifications
322